2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT MAINS/BRKRS. AIC ARTING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE: NEED TO SUBMIT RISER DIAGRAM
 SHOWING DEDICATED 20 AMP CIRCUT REQ`D
 PER 210-52D.
  
 3)PLEASE INCLUDE COLD WATER PIPE AS PART
 OF GROUNDING ELECTRODE SYSTEM. PLEASE
 SHOW ON RISER DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN