Plan Review Notes For Permit 99111338 |
Permit Number |
99111338 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO**************** | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF ALL | | EQUIPMENT MAINS/BRKRS. AIC ARTING IS | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | | 2)NOTE: NEED TO SUBMIT RISER DIAGRAM | | SHOWING DEDICATED 20 AMP CIRCUT REQ`D | | PER 210-52D. | | | | 3)PLEASE INCLUDE COLD WATER PIPE AS PART | | OF GROUNDING ELECTRODE SYSTEM. PLEASE | | SHOW ON RISER DIAGRAM. | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE FIRST | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|