Plan Review Notes For Permit 99111320 |
Permit Number |
99111320 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | THE PLANS NEEDS TO HAVE PERSONAL | | SIGNATURE OVER THE RAISE SEAL OF THE | | ARCHITECT. | | | | THE GUEST SUITE WINDOWS ARE REQUIRED TO | | PROVIDE THE EGRESS REQUIREMENTS STATED | | IN SECTION 1005.4.4 SBC 1997. NOTE PGT | | WINDOW SIZE OF 24SH DOES NOT MEET THE | | CODE REQUIREMENT. | | | | THE US TRUSS LAYOUT PLAN ILLUSTRATES A | | 2 STORY STRUCTURE AND THE ARCHITECT | | PALNS SPECIFY A ONE STORY STRUCTURE. | | | | THE FRONT DOOR IS REQUIRED TO PROVIDE A | | MINIUM 32" CLEAR OPENING WHEN ONE LEAF | | IS OPEN. | | | | PROVIDE PRODUCT APPROVAL FOR THE EXTERIO | | SWING DOORS. | | | | THE DESIGN COMPLIANCE FORM SPECIFYS THAT | | THE STRUCTURE WAS DESIGNED ACCORDING TO | | THE INVALID CODE EDITION, SBC 1994. NOTE | | THAT THE CURRENT CODE EDITION IS THE | | 1997 SBC. ATTACHED IS A COPY OF THE | | UPDATED DESIGN COMPLIANCE FORM. | | | | CLARIFY THE HEIGHT AND WIDTH DEMINSION | | FOR THE F1 FOOTER. |
|