Plan Review Notes
Plan Review Notes For Permit 99111320
Permit Number 99111320
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************UNSAT*********************
  
 1)NOTE: NEED TO SUBMIT AIC RATING WITH
 ALL DRAWINGS. NEED TO AIC RATING FOR
 ALL EQUIPMENT MAINS/BKRS AS PER 110-9
 215-5. AIC RATING IS FIGURED FROM FAULT
 CURRENT CALCULATIONS.
  
 2)NOTE;EQUIPMENT GROUND REQ`D BETWEEN
 MAIN DISC. AND PANEL SIZE PER 250-95.
  
 3)NOTE:AS REQ`D BY 250-81/215-5 PLEASE
 SHOW BDLG.STEEL AS PART OF THR GROUNDING
 ELECTRODE SYSTEM.
  
 4)NOTE:AS REQ`D BY 215-5/210-52D PLEASE
 SHOW DEDICATED BATH(S) 20AMP CIRCUT ON
 PANEL SCHEDULE.
  
 5)NOTE:AS REQ`D PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW RES. DWELLINGS.
  
 6)NOTE: PLEASE DELETE ALL ITEMS THAT ARE
 NOT STAYING ON PANEL SCHEDULE. PLEASE
 CLEAN UP AND REDRAW. CLEAN UP ANY
 SHADED AREAS ON PLANS THAT ARE NOT MEANT
 TO BE THERE.
  
  
 PLEASE SUBMIT THE ABOVEINFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS; 659-8096 EXT 8372