Plan Review Notes For Permit 99111320 |
Permit Number |
99111320 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************UNSAT********************* | | | | 1)NOTE: NEED TO SUBMIT AIC RATING WITH | | ALL DRAWINGS. NEED TO AIC RATING FOR | | ALL EQUIPMENT MAINS/BKRS AS PER 110-9 | | 215-5. AIC RATING IS FIGURED FROM FAULT | | CURRENT CALCULATIONS. | | | | 2)NOTE;EQUIPMENT GROUND REQ`D BETWEEN | | MAIN DISC. AND PANEL SIZE PER 250-95. | | | | 3)NOTE:AS REQ`D BY 250-81/215-5 PLEASE | | SHOW BDLG.STEEL AS PART OF THR GROUNDING | | ELECTRODE SYSTEM. | | | | 4)NOTE:AS REQ`D BY 215-5/210-52D PLEASE | | SHOW DEDICATED BATH(S) 20AMP CIRCUT ON | | PANEL SCHEDULE. | | | | 5)NOTE:AS REQ`D PER 1993/1996 NFPA-72 | | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | IN NEW RES. DWELLINGS. | | | | 6)NOTE: PLEASE DELETE ALL ITEMS THAT ARE | | NOT STAYING ON PANEL SCHEDULE. PLEASE | | CLEAN UP AND REDRAW. CLEAN UP ANY | | SHADED AREAS ON PLANS THAT ARE NOT MEANT | | TO BE THERE. | | | | | | PLEASE SUBMIT THE ABOVEINFORMATION | | FOR REVIEW AND APPROVAL. IF THERE ARE | | ANY QUESTIONS; 659-8096 EXT 8372 |
|