Plan Review Notes For Permit 99111319 |
Permit Number |
99111319 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-STORM PANELS: | | -PROVIDE A COMPLETE INSTALLATION | | SCHEDULE AS PER CITY SAMPLE. | | -REVISE DESIGN PRESSURES HIGHLIGHTED ON | | SHEET 3 OF 5. SEE SHEET 5 OF 5 FOR | | CORRECT DESIGN PRESSURES. | | -SHEET 4 OF 5: HIGHLIGHT SPECIFIC | | CONNECTORS TO BE USED ACCORDING TO THE | | MOUNTING CONDITIONS, DESIGN PRESSURES, | | EDGE DISTANCE AND CONNECTION TYPE. | | 2-PROVIDE PRODUCT APPROVAL FOR: ENTRY | | DOORS (WITH LEGIBLE DRAWINGS), ARCHED | | WINDOWS, SLIDING GLASS DOORS WITH | | TRANSOM ABOVE ASSEMBLY. | | 3-UPDATE DESIGN CERTIFICATION FOR BLDG | | CODE COMPLIANCE FORM. | | 4-TRUSS DRAWINGS: | | -ENGINEER TO SIGN AND SEAL LAYOUT ALSO. | | -PROVIDE UPDATED TRUSS DRAWINGS USING | | SBC 1997 (NOT SBC 1991 OR SBC 1994) OR | | ASCE 7-95. | | -DESIGNER OF RECORD TO REVIEW ALL TRUSS | | DRAWINGS PRIOR TO SUBMITTAL. |
|