Plan Review Notes For Permit 99111288 |
Permit Number |
99111288 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT SQ.FOOTAGE OF SPACE AND OCCUPANT | | LOAD.COMPLY W/SPC TABLE 407 FOR NUMBER | | AND TYPE OF PLUMBING FIXTURES REQD. | | | | CLEARLY SHOW REQD.WHEELCHAIR TURNING | | SPACE IN TOILET ROOMS AS MANDATED IN | | FACBC SEC.4.2.3. | | | | SINK SHALL COMPLY W/FACBC SEC.4.24.1- | | 4.24.7. | | | | SUBMIT WATER RISER FOR REVIEW.COUNTYWIDE | | AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1. | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407. |
|