Plan Review Notes
Plan Review Notes For Permit 99110890
Permit Number 99110890
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT MANUFACTURERS SHEET FOR DENTAL
 CHAIRS,VACUUM PUMP,AIR COMPRESSORS AND
 ALL OTHER MEDICAL EQUIPMENT. COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1.
  
 CLEARLY SHOW DIMENSIONS OF NEW TOILET
 ROOM AND SHOW FIXTURE CLEARANCE OF H.C.
 WATER CLOSET AND SUBMIT DETAILS/HEIGHT
 DIMENSIONS OF ALL H.C.EQUIPMENT AND
 FIXTURES.COMPLY W/FACBC FOR NEW
 CONSTRUCTION 1997 ED.
  
 A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 AND SHALL BE H.C.ACCESSIBLEPER
 FACBC 4.1.3.(10)(A),4.15.
  
 SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/
 SPC TABLE 407 FOR AMOUNT OF PLBG.FIXS.
  
 SUBMIT DATA FROM MANUFACTURER REGARDING
 PH OF EFFLUENT FROM AUTO-PROCESSOR.
 ACCEPTABLE RANGE IS 5.0-10.0. A
 NEUTRALIZING TANK SHALL BE INSTALLED IF
 THIS RANGE CANNOT BE MAINTAINED PER
 SPC SEC.801.4.SUBMIT MANUF.SHEETS FOR
 PROCESSOR AND DEVELOPER.
  
 SUBMIT COPY OF CONTRACT FOR PROPER
 DISPOSAL OF PROCESSING CHEMICALS AND
 SILVER FROM DEVELOPING TANK.SPC 301.3.
  
 ALL SUBMITTED SHOP DWGS./MANUF.SHEETS
 SHALL BE LEGIBLE FOR REVIEW PER COUNTY-
 WIDE AMENDMENTS TO STD.PLBG.CODE SEC.
 104.2.1,104.2.2.
  
 SUBMIT SIGNED AND SEALED DRAWINGS FOR
 THE ENTIRE MEDICAL PIPING SYSTEM PER
 COUNTYWIDE AMENDMENTS TO STANDARD PLBG.
 CODE SEC.104.2.1.,104.2.3.COMPLY W/NFPA
 99.
  
 SIZE ALL THE VENTS ON THE SAN.RISER
 DIAGRAMS AND SUBMIT WATER RISER DIAGRAMS
 FOR ALL ALTERED PLBG PER COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE 104.2.1.,
 104.2.2.
  
 CLEARLY SHOW REQD.TURNING SPACE IN H.C.
 TOILET ROOM PER FACBC SEC.4.2.3.
  
  
 INDICATE PREVIOUS OCCUPANCY OF STRUCTURE
 IF THIS IS A CHANGE OF OCCUPANCY,THE
 BUILDING SHALL CONFORM TO THE INTENT OF
 THE TECHNICAL CODES AS REQD.BY THE
 BUILDING OFFICIAL PER SBC SEC.3401.2.2.1