2001-01-08 00:00:00ALL SHEETS OF THE STORM DRAINAGE
 CALCULATIONS SHALL BE SIGNED AND SEALED
 BY DESIGN PROFESSIONAL OF RECORD PER FL.
 ADMIN.CODE.
  
 THE GROUND LEVEL AREA DRAINS USED TO
 COLLECT THE STORM DRAINAGE OVEREFLOW
 FROM THE 5TH LEVEL SHALL BE SIZED PER
 SPC SEC.1109.3 & FIGURE 1109.3.THE SQ.
 FOOT AREA OF THE 5TH LEVEL MUST BE USED
 IN CONJUNCTION WITH THE FORMULA IN THE
 SPC.SEE SPC SEC.1108.2 AND TABLE 1108.2