Plan Review Notes For Permit 99110858 |
Permit Number |
99110858 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CORRECTED BY REVISIONS****************** | | | | 1)1997 SBC 411.5.4 REQUIRES GARAGES TO | | BE CONTINUOUSLY VENTILATED BY A MECHAN- | | ICAL SYSTEM WITH A POSITIVE MEANS FOR | | BOTH INLET AND EXHAUST OF AT LEAST 0.75 | | CFM PER SQ FT OF FLOOR AREA, 411.4.2 | | REQUIRES AT LEAST 6 AIR CHANGES PER HOUR | | F0R EACH LEVEL. PROVIDE CALCULATIONS | | SHOWING COMPLIANCE. | | 2) MECHANICAL PLANS SHOW C02 SENSOR, | | CODE REQUIRES REMOVAL OF PRODUCTS OF | | COMBUSTION. IS THIS SUPPLIMENTAL TO | | CONTINUOUS VENTILATION AS REQUIRED ABOVE | | AND WHAT FUNCTION DOES TIME CLOCK HOLD? | | 3) ACCESS DOORS REQUIRED FOR FIRE DAMPER | | ACCESS. PROVIDE DETAILS FOR REQUIRED | | FIRE DAMPER ACCESS |
|