2001-01-08 00:00:00CORRECTED BY REVISIONS******************
  
 1)1997 SBC 411.5.4 REQUIRES GARAGES TO
 BE CONTINUOUSLY VENTILATED BY A MECHAN-
 ICAL SYSTEM WITH A POSITIVE MEANS FOR
 BOTH INLET AND EXHAUST OF AT LEAST 0.75
 CFM PER SQ FT OF FLOOR AREA, 411.4.2
 REQUIRES AT LEAST 6 AIR CHANGES PER HOUR
 F0R EACH LEVEL. PROVIDE CALCULATIONS
 SHOWING COMPLIANCE.
 2) MECHANICAL PLANS SHOW C02 SENSOR,
 CODE REQUIRES REMOVAL OF PRODUCTS OF
 COMBUSTION. IS THIS SUPPLIMENTAL TO
 CONTINUOUS VENTILATION AS REQUIRED ABOVE
 AND WHAT FUNCTION DOES TIME CLOCK HOLD?
 3) ACCESS DOORS REQUIRED FOR FIRE DAMPER
 ACCESS. PROVIDE DETAILS FOR REQUIRED
 FIRE DAMPER ACCESS