2001-01-08 00:00:00CLEARLY SHOW LOCATION OF SCUPPERS ON
 PLANS.SIZE AND NUMBER SHALL COMPLY W/SBC
 SEC.1517.6.4.,1517.6.4.2, AND SPC SEC.
 1109.1- 1109.3.,& APPENDIX "A".
  
 SHT.PD-P3.01-15" STORM DRAIN IS DRAINING
 INTO A 10"LINE.SPC 307.5.,709.1.(SEE
 COLS.C-5.2).
  
 SIZE THE UNDERGROUNDHORIZONTAL SECTION
 FOR ALL THE STORM RISERS.COMPLY W/SPC
 SEC.1108.2 AND TABLE 1108.2.
  
 CLEARLY SHOW ON PLAN THAT CALCULATIONS
 FOR STORM DRAINAGE HAVE INCLUDED 1/2 THE
 AREA OF ALL PARAPET WALLS PER SPC SEC.
 1108.3.