2001-01-08 00:00:00****************DENIED******************
 1)PROVIDE CALCULATIONS SHOWING COMPLI-
 ANCE WITH 1997 SBC 411.4.2
 2)PROVIDE SEQUENCE OF OPERATON FOR REQ'D
 VENTILATION AND SYSTEM TO BE CONNECTED
 TO EMERGENCY POWER SYSTEM
 3)IS VENT SHAFT RATED? IF RATED PROVIDE
 DETAIL FOR PROTECTION OF OPENINGS AT
 EXHAUST FAN PENETRATION