Plan Review Notes For Permit 99110858 |
Permit Number |
99110858 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1-PAGE PD-E3.05 | | STAIR TOWERS 1 AND 3 NEED EXIT LIGHT | | THAT ARE W/P110-3B,11 | | | | 2-PAGE PD-E5.01 | | TRANSFER SWITCH NEEDS A DISCONNECT | | ON THE LINE SIDE OF THE TRANSFER | | SWITCH225-8 | | | | 3-PAGE PD-E5.03 | | SUBMIT A LOAD CALCULATION PER 215-5 | | FOR THE MAIN FEEDERS TO THE BUILDING | | | | 4-PAGE PD-E4.03 | | ALL OUTLETS OUTSIDE ON ROOF LEVEL TO | | BE G.F.C.I. PROTECTED. | | | | 5-PROVIDE THIS INFORMATION PRIOR TO | | FIRST ELECTRICAL ROUGH INSPECTION! |
|