Plan Review Notes For Permit 99110657 |
Permit Number |
99110657 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************PROVISO******************* | | | | 1)NOTE: NEED TO SHOW AIC RATING OF | | EQUIPMENT MAINS AND BRANCH BRKRS. | | 2)NOTE:SHOW WIRE SIZE FOR SERVICE ON | | RISER DIAGRAM.215-5 | | 3)NOTE:SHOW COMPLETE GROUNDING ELECTRODE | | SYSTEM TO INCLUDE GROUND ROD,COLD WATER, | | AND BLDG.STEEL. AS PER 250-81/215-5 | | 4)NOTE:AS PER 210-52D/215-5 NEED TO SHOW | | SEPARATE 20AMP BRANCH CIRCUT ON PANEL | | SCHEDULE FOR BATH GFI/S | | 5)NOTE:AS PER 210-8-A-6 ALL OUTLETS | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | GFI/GFI PROTECTED. | | 6)NOTE:CHECK KITCHEN COUNTERSPACE FOR | | REQ`D OUTLET SPACING AS PER 210-52C | | 7)NOTE; MISSING OUTLET AS REQ`D BY | | 210-52 IN BEDROOM #2 | | | | 8)NOTE:NEW CONS./SMOKE DETECTORS ARE | | REQ`D INSIDE AND OUTSIDE ALL SLEEPING | | ROOMS AS PER NFPA-72 1993/1996 | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE FIRST | | ROUGH ELECTRICAL ISPECTION IS CALLED IN. |
|