Plan Review Notes
Plan Review Notes For Permit 99110657
Permit Number 99110657
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE: NEED TO SHOW AIC RATING OF
 EQUIPMENT MAINS AND BRANCH BRKRS.
 2)NOTE:SHOW WIRE SIZE FOR SERVICE ON
 RISER DIAGRAM.215-5
 3)NOTE:SHOW COMPLETE GROUNDING ELECTRODE
 SYSTEM TO INCLUDE GROUND ROD,COLD WATER,
 AND BLDG.STEEL. AS PER 250-81/215-5
 4)NOTE:AS PER 210-52D/215-5 NEED TO SHOW
 SEPARATE 20AMP BRANCH CIRCUT ON PANEL
 SCHEDULE FOR BATH GFI/S
 5)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 6)NOTE:CHECK KITCHEN COUNTERSPACE FOR
 REQ`D OUTLET SPACING AS PER 210-52C
 7)NOTE; MISSING OUTLET AS REQ`D BY
 210-52 IN BEDROOM #2
  
 8)NOTE:NEW CONS./SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS AS PER NFPA-72 1993/1996
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL ISPECTION IS CALLED IN.