Plan Review Notes
Plan Review Notes For Permit 99110632
Permit Number 99110632
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLAN A2 WALL SECTION, SPECIFY THE BELOW
 GRADE AND ABOVE GRADE DIMENSION FOR THE
 FOOTER.
  
 PLAN A2, CLARIFY THE METHOD AND TYPE OF
 ROOF TILE TO BE USED. NOTE THE PRODUCT
 APPROVAL SUBMITTED IS FOR THE HIGH
 PROFILE SPANISH S.
  
 DELETE THE EXPIRED MASTER PERMIT NUMBER
 NOTED ON PLANS A2.
  
 PLAN SD2, THE DOOR/WINDOW FASTENING
 SCHEDULE SHOULD BE DELETED AND THESE
 COMPONETS WILL BE REQUIRED TO BE
 INSTALLED AS PER THE SITE SPECIFIC
 ENGINEERING WHICH IS SUBMITTED WITH THE
 PERMIT APPLICATION.
  
  
 THE SIDE ELEVATION WITH A TYPICAL 7'6"
 SIDE SETBACK DOES NOT COMPLY WITH TABLE
 600. WALL AREA = 388SF X 20%= 77'6".
 WALL OPENINGS= 98'6"
 OPENINGS EXCEED ALLOWED AMT BY 21SF.
 ELEVATION WITH ENCLOSED LANI:
 476SF X 20%= 95SF
 WALL OPENINGS= 98'6"
 OPENINGS EXCEED ALLOWED AMT BY 3'6".
  
 SEE PLAN REVIEW COMMENTS FROM ELECTRIC
 AND PLUMBING
  
 DELETE LIVINGSTON LANE FROM THE COVER
 PLAN.
  
 PROVIDE TRUSS ENGINEERING FOR REVIEW.