Plan Review Notes For Permit 99110631 |
Permit Number |
99110631 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************* UNSAT ******************* | | | | 1)NOTE:GROUNDING ELECTRODE CONDUCTOR IS | | TO GO TO TWO METHODS OF GROUNDING | | ELECTRODES!! TO GROUND ROD,,,AND BLDG. | | STEEL AND ALL COLD WATER PIPES IN ANY | | DWELLING MUST BE BONDED TO THE ELEC. | | SYSTEM.**250-80**250-81-A** PLEASE SHOW | | ALL ON RISER DIAGRAM 215-5. | | | | 2)NOTE:SMOKE DETECTORS NEED TO BE MOVED | | TO BE INSIDE BEDROOMS. AS REQ`D BY 1993/ | | 1996 NFPA-72 2-2.1.1.1. | | | | JUST NOTE IF PVC CONDUIT IS USED BETWEEN | | MAIN DISC. AND PANEL ??? THEN AN EQUIP. | | GROUNDING CONDUCTOR NEEDS TO BE SIZED | | AND INSTALLED. | | | | PLEASE SUBMIT THE ABOVE INFROMATION | | FOR REVIEW AND APPROVAL BEFORE MASTER | | IS ISSUED. |
|