Plan Review Notes For Permit 99110631
Permit Number 99110631
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE:GROUNDING ELECTRODE CONDUCTOR IS
 TO GO TO TWO METHODS OF GROUNDING
 ELECTRODES!! TO GROUND ROD,,,AND BLDG.
 STEEL AND ALL COLD WATER PIPES IN ANY
 DWELLING MUST BE BONDED TO THE ELEC.
 SYSTEM.**250-80**250-81-A** PLEASE SHOW
 ALL ON RISER DIAGRAM 215-5.
  
 2)NOTE:SMOKE DETECTORS NEED TO BE MOVED
 TO BE INSIDE BEDROOMS. AS REQ`D BY 1993/
 1996 NFPA-72 2-2.1.1.1.
  
 JUST NOTE IF PVC CONDUIT IS USED BETWEEN
 MAIN DISC. AND PANEL ??? THEN AN EQUIP.
 GROUNDING CONDUCTOR NEEDS TO BE SIZED
 AND INSTALLED.
  
 PLEASE SUBMIT THE ABOVE INFROMATION
 FOR REVIEW AND APPROVAL BEFORE MASTER
 IS ISSUED.