Plan Review Notes
Plan Review Notes For Permit 99110631
Permit Number 99110631
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************UNSAT**********************
  
 1)NOTE:AS PER 110-9/215-5 NEED TO SUBMIT
 AIC RATING OF EQUIPMENT MAINS, BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 2)NOTE: AS PER 210-52D/215-5 NEED TO
 SHOW BATH(S) DEDICATED GFI CIRCUT ON
 PANEL SCHEDULE.
  
 3)NOTE:AS PER 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS IN NEW DWELLINGS.
  
 4)NOTE:RISER DIAGRAM SHOWS ALUM. AS PART
 FO THE GROUNDING ELECTRODE,, AS PER
 COUNTY AMENDMENT THIS IS NOT ALLOWED.
 ONLY COPPER OR GALV.
  
 5)NOTE:AS PER NEC TABLES 4/5 PIPE FILL
 FOR THE CONDUIT FEEDING POOL PANEL
 IS NOT LARGE ENOUGH. PLEASE CORRECT AND
 CHANGE CONDUIT SIZE.
  
 6)NOTE:AS PER 210-52E NEED TO HAVE REC.
 IN FRONT OF DWELLING.
  
 7)NOTE: NEC. REQ`S ROOM FOR TWO SPARE
 CIRCUTS IN ALL PANELS OF NEW HOMES.
 YOUR PLANS SHOW LOAD CALCULATION BEING
 123.8 AMPS AND UTILIZING 125 AMP PANEL.
 THIS PANEL IS NOT LARGE ENOUGH AND NEEDS
 TO INCREASE TO 150. ALSO THIS DOES NOT
 EVEN INCLUDE POOL PANEL OPTION???!!!!
 NEED TO SUBMIT LOAD CALCULATION SHOWING
 POOL PANEL OPT. TO INCLUDE POOL HEATER,
 POOL LIGHT, AND POOL PUMP ETC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL AT 659-8096
 EXT 8372