2001-01-08 00:00:00THE PERCENTAGE OF WALL OPENINGS EXCEED
 THE AMOUNT ALLOWED BY TABLE 600.
 PLAN A3 SIDE ELEVATION, WALL AREA
 388SF X 20%= 77.6SF ALLOWED
 OPENINGS:8X4'6= 36
 4X4'6= 18
 3X4'6= 13.5
 DOOR4'6X7= 31.5
 4X4'6= 18
 TOTAL117SF
 117-77.6= 39.5SF OVER ALLOWED AMOUNT
  
 ENCLOSED LANI SIDE:
 ADD 12X8X20%=19.2SF ADD TO 77.6= 96.8
 117-96.8= 20.2SF OVER ALLOWED AMOUNT
  
 PROVIDE SITE SPECIFIC ENGINEERING
 CALCULATIONS FOR THE EXTERIOR WINDOWS &
 SLIDING GLASS DOORS WITH EACH PERMIT
 APPLICATION.
  
 SEE COMMENTS FROM PLUMBING AND ELECTRIC
 REVIEW.
  
 PLAN SD1, SD2, SD3, SD4 UPDATE PLAN DATE
  
 REMOVE OLD MASTER PERMIT NUMBER FROM
 PLAN SD2 AND SD4.
  
 PROVIDE A TRUSS DESIGN CERTIFICATION
 FORM FOR THE TRUSS ENGINEERING. ATTACHED
 IS A COPY OF THE FORM.