Plan Review Notes For Permit 99110631 |
Permit Number |
99110631 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | THE PERCENTAGE OF WALL OPENINGS EXCEED | | THE AMOUNT ALLOWED BY TABLE 600. | | PLAN A3 SIDE ELEVATION, WALL AREA | | 388SF X 20%= 77.6SF ALLOWED | | OPENINGS:8X4'6= 36 | | 4X4'6= 18 | | 3X4'6= 13.5 | | DOOR4'6X7= 31.5 | | 4X4'6= 18 | | TOTAL117SF | | 117-77.6= 39.5SF OVER ALLOWED AMOUNT | | | | ENCLOSED LANI SIDE: | | ADD 12X8X20%=19.2SF ADD TO 77.6= 96.8 | | 117-96.8= 20.2SF OVER ALLOWED AMOUNT | | | | PROVIDE SITE SPECIFIC ENGINEERING | | CALCULATIONS FOR THE EXTERIOR WINDOWS & | | SLIDING GLASS DOORS WITH EACH PERMIT | | APPLICATION. | | | | SEE COMMENTS FROM PLUMBING AND ELECTRIC | | REVIEW. | | | | PLAN SD1, SD2, SD3, SD4 UPDATE PLAN DATE | | | | REMOVE OLD MASTER PERMIT NUMBER FROM | | PLAN SD2 AND SD4. | | | | PROVIDE A TRUSS DESIGN CERTIFICATION | | FORM FOR THE TRUSS ENGINEERING. ATTACHED | | IS A COPY OF THE FORM. |
|