2001-01-08 00:00:00***************UNSAT********************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE: NEED TO INCLUDE AS PART OF THE
 GROUNDING ELECTRODE SYSTEM; GRND.ROD,
 BLDG.STEEL AND COLD WATER PIPE. AS PER
 250-81.
  
 3)NOTE: AS REQ`D BY 210-52D/215-5 NEED
 TO INCLUDE ON PANEL SCHEDULE BATH(S)
 DEDICATED 20AMP GFI CIRCUT(S).
  
 4)NOTE: AS PER NEC AND 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ANY
 QUESTIONS CALL 659-8096 EXT.8372