2001-01-08 00:00:00 | WALL SECTION 3/A2 & 2/A2, THE FOOTER IS |
| REQUIRED TO BE A MININUM OF 12" BELLOW |
| AND 4" ABOVE FINISH GRADE. |
| SECT 1804.1.3 SBC 1997 |
| |
| WALL SECTION 3/A2 SPECIFYS SIMULATED |
| STUCCO, PROVIDE MORE INFO.THE MININUM |
| STUCCO THICKNESS REQUIRED IS 5/8". |
| CLARIFY THE WALL FINISH. |
| SECT 2504.2.1SBC 1997 |
| |
| WALL SECT 3/A2, PROVIDE FIREBLOCKING IN |
| THE CONCEALED SPACE AT THE WALL CEILING |
| CONNECTION.SECT 2305.1.1SBC 1997 |
| |
| PLAN T1, SPECIFYS THE INCORRECT BUILDING |
| CODE EDITION. |
| |
| SECTION 2/A2, SPECIFY WHICH METHOD OF |
| ATTACHMENT WILL BE USED FOR INSTALLING |
| THE ROOF TILE.NOTE THIS NEEDS TO BE |
| COORDINATED WITH THE PRODUCT APPROVAL |
| REQUIREMENTS. |
| |
| |
| CLARIFY THE NAILING REQUIREMENTS FOR |
| ATTACHING THE ROOF SHEATHING.NOTE THE |
| CODE AMENDMENTS REQUIRE A MIN OF 8D |
| COMMON NAILS EVERY 4"OC @ EDGES & 6"OC |
| @ FIELD.SECT 2306.1 CITY AMEND |
| |
| THE NORANDEX WINDOWS AND DOORS ASSEMBLYS |
| WILL BE REQUIRED TO BE PROVIDED WITH |
| SITE SPECIFIC ENGINEERING WITH EACH |
| PERMIT APPLICATION.SECT 1704.4 CITY AM |
| |
| PLAN A1,WINDOW & DOOR ATTACHMENT WILL BE |
| AS REQUIRED BY THE SITE SPECIFIC ENGINEE |
| RING. THE PLAN SHOULD CLEARLY SPECIFY |
| THE SUB-BUCK ATTACHMENT TO THE STRUCTURE |
| ONLY. |
| |
| |
| |
| |
| PROVIDE ENGINEERING FOR THE BUTT GLAZED |
| WINDOW SYSTEM. SECT 1707.4 CITY AMEND |
| |
| THE TRUSS ENGINEERING SHEETS ARE REQUIRE |
| TO HAVE THE ORIGINAL PERSONAL SIGNATURE |
| AND RAISED SEAL ON--EVERY-- SHEET. IN |
| LIEW OF THIS A TRUSS DESIGN CERTIFICATIO |
| FORM MAY BE SUBMITTED.ATTACHED IS A |
| SAMPLE FORM. |
| |
| SEE PLAN REVIEW COMMENTS FROM ELECTRIC |
| AND PLUMBING. |
| |
| THE PERMIT VALUE WILL BE AS PER THE |
| FOLLOWING CALCULATIONS: |
| A/C AREA 2547 X 67.20 =$171,158.40 |
| ROOF AREA 783 X 36.75 = 28,752.25 |
| TOTAL $199,911 |