Plan Review Notes
Plan Review Notes For Permit 99110356
Permit Number 99110356
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 AS PER ART; 110-9/215-5
  
 2)NOTE:AS PER 1993/1996 NFPA-72 2-2.1.1
 .1 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS OF NEW
 DWELLINGS.
  
 3)NOTE:AS PER 210-52D PLEASE INCLUDE
 BATH(S) GFI CIRCUT ON PANEL SCHEDULE.
 20 AMP,#12 AWG. DEDICATED.
  
 4)NOTE:AS PER 210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 5)NOTE: PLANS SHOW MAIN DISCONNECT NEXT
 TO METERCAN,,,,,POWER RISER SHOWS NO
 MAIN?? WHICH IS IT? ALSO IF 200 AMP
 SERVICE IS GOING TO BE AN OPTION THEN
 DRAW SECOND RISER WITH WIRE SIZES,
 CONDUIT SIZE, AND APPRO. GROUND.
  
 6)NOTE: AS PER 250-81/215-5 PLEASE INCL.
 COLD WATER PIPE AS PART OF THE GROUNDING
 SYSTEM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN. THIS
 WOULD INCLUDE GROUND ROUGH IF ANY.