Plan Review Notes
Plan Review Notes For Permit 99110353
Permit Number 99110353
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS. TO INCLUDE BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS. REQUESTED AS PER 110-9/
 215-5
  
 2)NOTE: AS PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS IN
 NEW DWELLINGS.
  
 3)NOTE:AS REQ`D PER ARTS:210-52D/215-5
 PLEASE INCLUDE DEDICATED BATH GFI CIRCUT
 (S) ON PNAEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICALINSPECTION IS CALLED IN.