2001-01-08 00:00:00 | LOCATION,TYPE AND AMOUNT OF FIXTURES ON |
| THE SANITARY RISER DIAGRAMS DO NOT MATCH |
| THE FLOOR PLAN.SUBMIT REVISED SANITARY |
| RISER DIAGRAMS.COUNTYWIDE AMENDMENTS TO |
| SPC SEC.104.2.1. |
| |
| THE BOTTOM OF THE WOOD BLOCKING BEHIND |
| AND ON THE SIDE OF THE WATER CLOSET |
| SHALL BE MAX.32" AFF.PER FAIR HOUSING |
| ACT SEC.100.205 REQUIREMENT #6. |
| |
| ALL BATHROOMS WITHIN THE COVERED |
| DWELLING UNIT SHALL COMPLY WITH THE |
| PROVISIONS OF THE FEDERAL FAIR HOUSING |
| ACT SECTION 3,24 CFR 100.205(C)(3)(IV) |
| REQUIREMENT#7(2)PARAGRAPH (A)OR(B). |
| CLEAR FLOOR SPACE SHALL BE PROVIDED AT |
| FIXTURES TO ALLOW A PERSON IN A WHEEL- |
| CHAIR OR OTHER MOBILITY AID USE OF THE |
| FIXTURES.THE CLEAR FLOOR SPACE SHALL BE |
| SHOWN ON THE PLANS AND DESIGNATE WHICH |
| OPTION OF #7 (A OR B)IS BEING USED. |
| |
| CLEARLY SHOW WIDTH OF KIT.AREA BETWEEN |
| CABINETS.COMPLY W/FEDERAL FAIR HOUSING |
| ACT SEC.100.205 REQ.#7 (1)(C).SHOW 60" |
| TURNING RADIUS ON PLANS. |
| |
| CLEAR FLOOR SPACE FOR RANGE SHALL BE |
| CENTERED ON THE APPLIANCE PER FAIR |
| HOUSING ACT REQ.#7 (1)(A).(SEE UNITS |
| 1-L,2-L,1-R.SHOW THE CLEAR FLOOR SPACE |
| ON THE PLANS. |