Plan Review Notes
Plan Review Notes For Permit 99110144
Permit Number 99110144
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00LOCATION,TYPE AND AMOUNT OF FIXTURES ON
 THE SANITARY RISER DIAGRAMS DO NOT MATCH
 THE FLOOR PLAN.SUBMIT REVISED SANITARY
 RISER DIAGRAMS.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 THE BOTTOM OF THE WOOD BLOCKING BEHIND
 AND ON THE SIDE OF THE WATER CLOSET
 SHALL BE MAX.32" AFF.PER FAIR HOUSING
 ACT SEC.100.205 REQUIREMENT #6.
  
 ALL BATHROOMS WITHIN THE COVERED
 DWELLING UNIT SHALL COMPLY WITH THE
 PROVISIONS OF THE FEDERAL FAIR HOUSING
 ACT SECTION 3,24 CFR 100.205(C)(3)(IV)
 REQUIREMENT#7(2)PARAGRAPH (A)OR(B).
 CLEAR FLOOR SPACE SHALL BE PROVIDED AT
 FIXTURES TO ALLOW A PERSON IN A WHEEL-
 CHAIR OR OTHER MOBILITY AID USE OF THE
 FIXTURES.THE CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE PLANS AND DESIGNATE WHICH
 OPTION OF #7 (A OR B)IS BEING USED.
  
 CLEARLY SHOW WIDTH OF KIT.AREA BETWEEN
 CABINETS.COMPLY W/FEDERAL FAIR HOUSING
 ACT SEC.100.205 REQ.#7 (1)(C).SHOW 60"
 TURNING RADIUS ON PLANS.
  
 CLEAR FLOOR SPACE FOR RANGE SHALL BE
 CENTERED ON THE APPLIANCE PER FAIR
 HOUSING ACT REQ.#7 (1)(A).(SEE UNITS
 1-L,2-L,1-R.SHOW THE CLEAR FLOOR SPACE
 ON THE PLANS.