Plan Review Notes For Permit 99110144 |
Permit Number |
99110144 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT DETAIL OF REINFORCEMENT OF WALLS | | FOR FUTURE INSTALLATION OF GRAB BARS AS | | REQD.BY FEDERAL FAIR HOUSING ACT SECTION | | 3, 24 CFR 100.205 (C)(3)(III). | | NOTE:ALL BATHROOMS WITHIN THE COVERED | | DWELLING UNIT SHALL COMPLY. | | | | ALL BATHROOMS WITHIN THE COVERED | | DWELLING UNIT SHALL COMPLY WITH THE | | PROVISIONS OF THE FEDERAL FAIR HOUSING | | ACT SECTION 3, 24 CFR 100.205 (C)(3)(IV) | | REQ.#7(2)PARAGRAPH (A)OR(B).CLEAR FLOOR | | SPACE SHALL BE PROVIDED AT FIXTURES TO | | ALLOW A PERSON IN A WHEELCHAIR OR OTHER | | MOBILITY AID USE OF THE FIXTURES.CLEAR | | FLOOR SPACE SHALL BE SHOWN ON THE PLANS | | AND DESIGNATE WHICH OPTION OF | | REQUIREMENT #7 (A OR B)IS BEING USED. | | | | SANITARY RISERS SHALL CORRELATE W/ FLOOR | | PLAN. CITY OF WPB AMENDMENTS TO SPC SEC. | | 104.2.1. | | | | WET VENTS SHALL COMPLY W/SPC SEC911.1(1) | | (MAX.4 FIXTURE UNITS ON 2") |
|