2001-01-08 00:00:00***************PROVISO****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS, AS PER 110-9/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE: PLEASE SHOW ON PANEL SCHEDULE
 BATH CIRCUT(S) REQ`D AS PER ART:210-52D
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROAVL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN