Plan Review Notes For Permit 99101350 |
Permit Number |
99101350 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************PROVISO**************** | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | EQUIPMENT AND MAINS, AS PER 110-9/215-5 | | AIC RATING IS FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | 2)NOTE: PLEASE SHOW ON PANEL SCHEDULE | | BATH CIRCUT(S) REQ`D AS PER ART:210-52D | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROAVL BEFORE FIRST | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|