Plan Review Notes
Plan Review Notes For Permit 99101261
Permit Number 99101261
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS ASD PER 110-9/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:PANEL SCHEDULE NEEDS TO SHOW
 CIRCUT(S) FOR BATH AS PER 210-52D.
 3)NOTE:NEED TO SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO GROUND ROD AND BLDG.
 STEEL AS PER 250-81
 4)NOTE:ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 AS PER 210-8-A-6.
 5)NOTE:SMOKE DETECTOR ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AS PER
 1996 NFPA -72 2-2.1.1.1
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN