Plan Review Notes For Permit 99101261 |
Permit Number |
99101261 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************PROVISO******************* | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | EQUIPMENT AND MAINS ASD PER 110-9/215-5 | | AIC RATING IS FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | 2)NOTE:PANEL SCHEDULE NEEDS TO SHOW | | CIRCUT(S) FOR BATH AS PER 210-52D. | | 3)NOTE:NEED TO SHOW GROUNDING ELECTRODE | | CONDUCTOR GOING TO GROUND ROD AND BLDG. | | STEEL AS PER 250-81 | | 4)NOTE:ALL OUTLETS SERVING KITCHEN | | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED | | AS PER 210-8-A-6. | | 5)NOTE:SMOKE DETECTOR ARE REQ`D INSIDE | | AND OUTSIDE ALL SLEEPING ROOMS AS PER | | 1996 NFPA -72 2-2.1.1.1 | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE FIRST | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|