Plan Review Notes For Permit 99101252 |
Permit Number |
99101252 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO**************** | | | | 1)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | GFI/GFI PROTECTED. | | 2)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE | | AND OUTSIDE ALL SLEEPING ROOMS. AS PER | | 1996 NFPA-72 2-2.1.1.1 | | 3)NOTE:PANEL SCHED. NEEDS TO SHOW CIRCUT | | REQ`D BY 210-52D FOR BATH(S). | | 4)NOTE:NEED TO SHOW GROUNDING ELECTRODE | | CONDUCTOR GOING TO GROUND ROD AND BLDG. | | STEEL. AS PER ART:250-81 | | 5)NOTE:NEED TO SUBMIT AIC RATING OF | | EQUIPMENT MAINS AS PER 110-9/215-5 | | AIC RATING IS FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE FIRST | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|