2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 2)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS. AS PER
 1996 NFPA-72 2-2.1.1.1
 3)NOTE:PANEL SCHED. NEEDS TO SHOW CIRCUT
 REQ`D BY 210-52D FOR BATH(S).
 4)NOTE:NEED TO SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO GROUND ROD AND BLDG.
 STEEL. AS PER ART:250-81
 5)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AS PER 110-9/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN