Plan Review Notes
Plan Review Notes For Permit 99101250
Permit Number 99101250
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT BEING INSTALLED. AIC RATINGS
 ARE FIGURED FROM FAULT CURRENT CALCU-
 LATIONS. ABOVE PER ARTS:110-9/215-5
 2)NOTE:AS PER ART:250-81 NEED TO SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 GROUND ROD AND BUILDING STEEL ALSO.
 3)NOTE:PANEL SCHEDULE TO SHOW CIRCUT
 REQ`D FOR BATH(S) CIRCUT AS PER ART:
 210-52D.
 4)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE:AS PER 1996 NFPA-72 CHAPTER ;
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN CONSTRUCTION OF NEW HOMES.
  
 NEED TO REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN.