Plan Review Notes For Permit 99101158 |
Permit Number |
99101158 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *****************PROVISO**************** | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | EQUIPMENT AND MAINS FIGURED FROM FAULT | | CURRENT CALCULATIONS. AS PER ARTS: | | 110-9/215-5 | | 2)NOTE:NEED TO LIST ON PANEL SCHED. | | CIRCUT FOR BATH(S) AS PER ART:210-52D | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE FIRST | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|