1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************PROVISO****************** | | | | 1)NOTE:PLEASE SUBMIT AIC RATING OF | | EQUIPMENT FIGURED FROM FAULT CURRENT | | CALCULATIONS.AS PER 110-9/215-5 | | ALSO PLEASE LIST ON ALL PANEL SCHEDULES | | CIRCUTFOR BATH GFI`S AS PER 210-52D. | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE ROUGH | | INSPECTION IS CALLED IN. |
|