Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "A0". PROVIDE ELEVATION
 CERTIFICATE.
 2-REVISE FOOTING F-6. 16" MINIMUM DEPTH
 SEC 1804.1.3 SBC 1997 AND SEC 1804.1.9
 CITY AMENDMENTS TO SBC 1997.
 3-REVISE SIZE OF CEILING FANS. TABLE 6-6
 FLORIDA ENERGY CODE, 1997 EDITION.
 4-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY AND
 PRODUCT APPROVAL FOR FRENCH DOOR AT
 MASTER SUITE.
 5-SEE COMMENTS ON PLANS AND REVISE ALL
 ORIGINAL DRAWINGS AS REQUIRED AND
 RESUBMIT TO THIS OFFICE.
 6-PROVIDE SIGNED, SEALED AND DATED SOIL
 TEST REPORT (ORIGINAL) AND COPIES OF
 THE TESTS PERFORMED.
 7-STORM PANELS:
 REVISE INSTALLATION SCHEDULE AND KEY
 PLAN TO MATCH ARCHITECT'S PLANS.
 HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TO BE USED ON THIS PROJECT.
 USE CITY UPDATED INSTALLATION
 SCHEDULE SAMPLE. (ATTACHED).
 8-REVISE SURVEY. ARCHITECT'S PLANS DON'T
 SHOW EXTENDED PATIO.