Plan Review Notes For Permit 99101147 |
Permit Number |
99101147 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************PROVISO******************* | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | EQUIPMENT AND MAINS.AS PER 110-9/215-5 | | AIC RATING IS FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | 2)NOTE:PLEASE SHOW ON PANEL SCHEDULE | | CIRCUT REQ`D FOR BATHS REQ`D AS PER ART; | | 210-52D | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE FIRST | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|