2001-01-08 00:00:00 | PRODUCT APPROVAL FOR THE SLIDING WINDOWS |
| IS EXPIRED.PROVIDE UPDATED REPORT. |
| |
| SLIDING WINDOWS ARE DESIGNED TO 75MPH & |
| 20PSF PRESSURE. PROVIDE PRODUCT DESIGNED |
| ACCORDING TO OUR WIND ZONE OF 110MPH AND |
| 30PSF AS PER THE ENGINEER DESIGN COMPLIA |
| NCE STATEMENT.1606 SBC 1997 |
| |
| THE ROOF PANELS ARE REQUIRED TO BE DESIG |
| FOR A MINIMUM 20PSF LIVE LOAD.2002.2AMEN |
| |
| THE ROOF PANELS ARE REQUIRED TO HAVE |
| TESTING AND COMPLY WITH CHAPTER 16 & 17 |
| OF THE STANDARD BUILDING CODE.2002.2AMEN |
| |
| THE WALL AREA LOCATED ABOVE THE 6'COMMON |
| WALL NEEDS TO BE OF 1 HOUR TYPE CONSTRUC |
| TION & HAVE NO OPENINGS.TABLE 600 SBC |
| |
| THE ROOF AREA FOR 4' FROM THE COMMON |
| WALL NEEDS TO BE OF FIRE RESISTANT CONST |
| RUCTION. 704.4.1 SBC 1997 |
| |
| WINDOWS REQUIRED TO HAVE HURRICANE |
| MISSLE IMPACT PROTECTION.1606.4 AMEND |
| |
| PLANS NEED PALM BEACH COUNTY IMPACT |
| REVIEW. |
| |
| THE ROOF STRUCTURE CANNOT OVERHANG THE |
| COMMON WALL. |
| |
| THIS SPACE WILL BE CONSIDERED LIVING |
| SPACE AND WILL REQUIRE ELECTRIC TO CODE |
| AND ENERGY CALCULATIONS. |
| |
| THE ENGINEER SHOP DRAWINGS PREPARED BY |
| N KHANAL PE IS DESIGNED FOR A SCREENED |
| STRUCTURE. PROVIDE A DRAWING ILLUSTRATIN |
| A STRUCTURE CAPABLE OF PROVIDING WIND - |
| RESISTANCE FOR A SOLID CLADDED ENCLOSURE |