2001-01-08 00:00:00PRODUCT APPROVAL FOR THE SLIDING WINDOWS
 IS EXPIRED.PROVIDE UPDATED REPORT.
  
 SLIDING WINDOWS ARE DESIGNED TO 75MPH &
 20PSF PRESSURE. PROVIDE PRODUCT DESIGNED
 ACCORDING TO OUR WIND ZONE OF 110MPH AND
 30PSF AS PER THE ENGINEER DESIGN COMPLIA
 NCE STATEMENT.1606 SBC 1997
  
 THE ROOF PANELS ARE REQUIRED TO BE DESIG
 FOR A MINIMUM 20PSF LIVE LOAD.2002.2AMEN
  
 THE ROOF PANELS ARE REQUIRED TO HAVE
 TESTING AND COMPLY WITH CHAPTER 16 & 17
 OF THE STANDARD BUILDING CODE.2002.2AMEN
  
 THE WALL AREA LOCATED ABOVE THE 6'COMMON
 WALL NEEDS TO BE OF 1 HOUR TYPE CONSTRUC
 TION & HAVE NO OPENINGS.TABLE 600 SBC
  
 THE ROOF AREA FOR 4' FROM THE COMMON
 WALL NEEDS TO BE OF FIRE RESISTANT CONST
 RUCTION. 704.4.1 SBC 1997
  
 WINDOWS REQUIRED TO HAVE HURRICANE
 MISSLE IMPACT PROTECTION.1606.4 AMEND
  
 PLANS NEED PALM BEACH COUNTY IMPACT
 REVIEW.
  
 THE ROOF STRUCTURE CANNOT OVERHANG THE
 COMMON WALL.
  
 THIS SPACE WILL BE CONSIDERED LIVING
 SPACE AND WILL REQUIRE ELECTRIC TO CODE
 AND ENERGY CALCULATIONS.
  
 THE ENGINEER SHOP DRAWINGS PREPARED BY
 N KHANAL PE IS DESIGNED FOR A SCREENED
 STRUCTURE. PROVIDE A DRAWING ILLUSTRATIN
 A STRUCTURE CAPABLE OF PROVIDING WIND -
 RESISTANCE FOR A SOLID CLADDED ENCLOSURE