Plan Review Notes For Permit 99100989 |
Permit Number |
99100989 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | NEED TO SUBMIT AIC RATING OF MAINS AND | | EQUIPMENT. AS PER 110-9/215-5 | | NEED TO SHOW GROUNDING ELECTRODE CONDUCT | | GOING TO BLDG. STEEL ASLO. AS PER 250-81 | | MISSING REC IN MASTER BATH GFI AS REQ`D | | PER 210-52D AND ATLEAST ONE 20AMP CIRCUT | | REQ`D TO BE LISTED ON PANEL SCHED. |
|