Plan Review Notes
Plan Review Notes For Permit 99100989
Permit Number 99100989
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00NEED TO SUBMIT AIC RATING OF MAINS AND
 EQUIPMENT. AS PER 110-9/215-5
 NEED TO SHOW GROUNDING ELECTRODE CONDUCT
 GOING TO BLDG. STEEL ASLO. AS PER 250-81
 MISSING REC IN MASTER BATH GFI AS REQ`D
 PER 210-52D AND ATLEAST ONE 20AMP CIRCUT
 REQ`D TO BE LISTED ON PANEL SCHED.