Plan Review Notes
Plan Review Notes For Permit 99100790
Permit Number 99100790
Review Stop M
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1) PROTECT OPEN ENDS OF DUCTS THAT ARE
 INSTALLED AT THIS PHASE
 2) OUTSIDE AIR OPENINGS ARE NOT TO BE
 LOCATED WITHIN 10 FT OF EXHAUST AIR OUT-
 LETS OR PLUMBING VENT STACKS
 3) APPLIANCES ON ROOF SHALL BE MIN. 18"
 ABOVE ROOF SURFACE. THIS DISTANCE IS
 MEASURED TO THE BOTTOM OF THE SUPPORT
 STRUCTURE OF THE STAND, NOT TO THE TOP
 4) NO OUTSIDE AIR INFORMATION IS PROVIDE
 WITH THIS PLAN. PROVIDE OUTSIDE AIR
 CALCULATIONS PER ASHRAE 62-89 AND AIR
 BALANCE SCHEDULE WITH PLANS FOR INTERIOR
 BUILD-OUT


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved