Plan Review Notes For Permit 99100790 |
Permit Number |
99100790 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ******CORRECTED BY LETTER ATTACHED****** | | EXHAUST FANS ARE NOT ALL INDICATED ON | | ROOF PROVIDE LOCATION FOR EACH FAN. | | PROVIDE AIR BALANCE SCHEDULE PER 1997 | | SMC 501.2 | | PROVIDE OUTSIDE AIR CALCULATIONS PER | | ASHRAE 62-89 | | EXHAUST AIR TOTALS IN BUILDING DOES NOT | | MATCH FAN CAPACITY ON SCHEDULE | | THIS INFORMATION IS FOR PERMIT NUMBER | | 99090252 BUILDOUT PERMIT |
|