Plan Review Notes
Plan Review Notes For Permit 99100534
Permit Number 99100534
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00HEIGHT OF HANDICAP WATER CLOSET SHALL
 COMPLY W/FACBC SEC.4.16.3.(17"-19")
  
 CLEAR FLOOR SPACE UNDER LAV.SHALL COMPLY
 W/FACBC SEC.4.19.2.(29" MIN)
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR WATER HEATER.COMPLY W/S.G.C.SEC.402
 & NFPA 54.
  
 GREASE INTERCEPTOR SHALL BE LOCATED OUT-
 SIDE OF BUILDING PER SPC SEC.1004.1
  
 SHOW FLOOR DRAINS ON RISER DIAGRAM.
  
 NOTE ON PLAN THAT GAS EQUIPMENT SHALL BE
 LISTED PER S.G.C. SEC.402.1,NFPA 54
 SEC.5.3.
  
 ANSUL VALVE SHALL BE LOCATED BELOW
 CEILING AND BE EQUIPPED W/UNION DOWN-
 STREAM OF SHUT-OFF VALVE.
  
 SUBMIT A WATER RISER FOR REVIEW .SPC
 SEC.607.1,COUNTYWIDE AMENDMENTS TO STD.
 PLBG.CODE SEC.104.2.1.
  
 INDIRECT WASTE RECEPTORS SHALL COMPLY
 W/SPC SEC.807.1.
  
 GREASE INTERCEPTORS SHALL BE LOCATED ON
 THE EXTERIOR OF THE BUILDING PER SPC SEC
 1004.1