Plan Review Notes For Permit 99100534 |
Permit Number |
99100534 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | HEIGHT OF HANDICAP WATER CLOSET SHALL | | COMPLY W/FACBC SEC.4.16.3.(17"-19") | | | | CLEAR FLOOR SPACE UNDER LAV.SHALL COMPLY | | W/FACBC SEC.4.19.2.(29" MIN) | | | | SUBMIT CALCULATIONS FOR COMBUSTION AIR | | FOR WATER HEATER.COMPLY W/S.G.C.SEC.402 | | & NFPA 54. | | | | GREASE INTERCEPTOR SHALL BE LOCATED OUT- | | SIDE OF BUILDING PER SPC SEC.1004.1 | | | | SHOW FLOOR DRAINS ON RISER DIAGRAM. | | | | NOTE ON PLAN THAT GAS EQUIPMENT SHALL BE | | LISTED PER S.G.C. SEC.402.1,NFPA 54 | | SEC.5.3. | | | | ANSUL VALVE SHALL BE LOCATED BELOW | | CEILING AND BE EQUIPPED W/UNION DOWN- | | STREAM OF SHUT-OFF VALVE. | | | | SUBMIT A WATER RISER FOR REVIEW .SPC | | SEC.607.1,COUNTYWIDE AMENDMENTS TO STD. | | PLBG.CODE SEC.104.2.1. | | | | INDIRECT WASTE RECEPTORS SHALL COMPLY | | W/SPC SEC.807.1. | | | | GREASE INTERCEPTORS SHALL BE LOCATED ON | | THE EXTERIOR OF THE BUILDING PER SPC SEC | | 1004.1 |
|