2001-01-08 00:00:00 | HEIGHT OF HANDICAP WATER CLOSET SHALL |
| COMPLY W/FACBC SEC.4.16.3. |
| |
| CLEAR FLOOR SPACE UNDER LAV.TO COMPLY W/ |
| FACBC SEC.4.19.2. |
| |
| SUBMIT COMPLETE GAS DRAWING FOR REVIEW. |
| SHOW TYPE OF PIPING,SIZES,BTU LOAD OF |
| EACH APPLIANCE AND TOTAL LOAD ON SYSTEM. |
| GAS SYSTEM SHALL BE SIZED IN ACCORDANCE |
| W/STD.PLBG.CODE SECS.305.4 AND TABLES |
| 305.4(A)- 305.4(F). |
| |
| GAS EQUIPMENT SHALL BE LISTED PER STD. |
| GAS CODE SEC.402.1 AND NFPA 54 SEC.5.3 |
| |
| SUPPLY CALCULATIONS FOR COMBUSTION AIR |
| PER STD.GAS CODE SEC.402.4. |
| |
| WALLS IN TOILET ROOMS SHALL BE NON- |
| ABSORBENT MATERIAL TO A HEIGHT OF 4'PER |
| SBC SEC.1204.2 |
| |
| MIN.SIZE GREASE TRAP SHALL BE 750 GALS. |
| PER HEALTH DEPT.REQS.RULE 10D-6.055(5). |
| |
| FLOOR DRAINS ARE REQD.IN THE TOILET |
| ROOMS PER SPC SEC.409.4.1.1. |
| |
| SUBMIT A WATER RISER DIAGRAM FOR REVIEW. |
| COMPLY W/SPC SEC.607.1,104.2.1. |
| |
| SHOW LOCATION OF DRINKING FOUNTAION ON |
| FLOOR PLAN.COMPLY W/FACBC SEC.4.1.3.(A). |
| FOR HANDICAP ACCESSIBILITY. |
| |
| SHOW LOCATION AND SIZES OF ALL INDIRECT |
| WASTES.COMPLY W/SPC SEC.801.3,804.1, |
| 805.1. |
| |
| INDIRECT WASTE RECEPTORS SHALL COMPLY |
| W/SPC SEC.807.1 |
| |
| NOTE:CONTACTED DEPT.OF BUS.REGULATION |
| REGARDING THEIR APPROVAL OF PLANS.SPOKE |
| W/MS.BARBARA GIBSON AND SHE STATED THEY |
| WERE TOLD BY OWNER THAT 51% OR MORE OF |
| HIS SALES WOULD BE FROM GROCERY SALES |
| SO THEIR DEPT.DOESN'T HAVE JURISDICTION. |
| DEPT.OF AGRICULTUREWILL INSPECT PRIOR |
| TO OPENING. |