Plan Review Notes
Plan Review Notes For Permit 99100534
Permit Number 99100534
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) LOAD CALCULATION NOT TO CODE60%????
  
 2) MAINS WILL HAVE TO BE GROUPED 230-72
  
 3) GROUND RODS TO BE TIED TOGETHER
 250-83
  
 4) SERVICE ENTRANCE CONDUCTORS AT
 WEATHER HEAD ARE TO BE TIED INTO THE
 SAME DROP FROM FPL!!230-2
  
 5) BRANCH CIRCUIT NUMBERS ARE TO BE ON
 PLAN SHOWING WHICH OUTLET,LIGHT,AC
 ARE ON THE CIRCUIT.110-22