Plan Review Notes For Permit 99100504 |
Permit Number |
99100504 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)SINK IN KITCHEN AREA SHALL COMPLY W/ | | FACBC SEC.4.24.1-4.24.7.SEE ROOM #207. | | | | 2)WATER HEATER SHALL BE READILY ACCESS- | | IBLE PER SPC SEC.501.7.SUPPLY FIXED | | LADDER AND PLATFORM OR RELOCATE WATER | | HEATER TO FLOOR. | | | | 3)ONLY 4 FIXTURES PERMITTED ON 1/2"H.W. | | COUNTYWIDE AMENDMENTS TO SPC SEC.607.7. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|