2001-01-08 00:00:00 | PASSED WITH PROVISOS: |
| |
| 1.IMPERVIOUS AREA COMPUTATIONS (NOT |
| SUPPLIED) PLEASE SUPPLY. |
| |
| 1.THE METER FOR THE BUILDING (1-1/2") |
| AND BACKFLOW PREVENTER HAVE BEEN MOVED, |
| BUT IT NOW SITS IN FRONT OF THE DOORWAY. |
| THE METER WILL NEED TO BE INSTALLED IN |
| THE CITY SIDEWALK AND THE BACKFLOW |
| PREVENTER MUST BE IN THE PLANTER, |
| IMMEDIATELY BEHIND THE SIDEWALK. |
| |
| |
| 2.IRRIGATION MUST (1") MUST BE LOCATED |
| IN THE CITY SIDEWALK, AT THE SAME |
| LOCATION AS THE BUILDING METER, NOT |
| WHERE IT IS SHOWN ON C-1 OR I-1. THE |
| BACKFLOW PREVENTER MUST BE IN THE |
| PLANTER, IMMEDIATELY BEHIND THE |
| SIDEWALK. |
| |
| 3.THERE IS A FIRE SPRINKLER HEAD |
| PLAN,SHEETS FS-1 & 2, BUT NO DRAWING AS |
| TO WHERE THEY WILL TIE-IN TO THE CITY |
| SYSTEM.IT IS SUGGESTED THAT THE |
| CONTRACTOR WHO INSTALLS THE DRINKING |
| WATER METER ALSO INSTALL THE FIRE LINE |
| SERVICE AT THE SAME TIME, TO SAVE TIME |
| AND MONEY. THERE WILL NEED TO BE A |
| DOUBLE CHECK DETECTOR CHECK INSTALLED ON |
| THE FIRE LINE IN THE PLANTER IMMEDIATELY |
| BEHIND THE SIDEWALK. |
| |
| 4.ALL BACKFLOW PREVENTERS WILL NEED TO |
| BE HIDDEN WITH LANDSCAPING. |
| |
| 5. THE DETAILS USED FROM THE UTILITIES |
| DEPARTMENT IS OLD ALL PIPE IN THE ROW ON |
| THE SANITARY MUST BE SDR 26, SEE SHEET |
| C-3. |
| |
| 6.A COPY OF THE WATER AND SANITARY AS- |
| BUILTS WILL NEED TO BE SUBMITTED TO |
| ENGINEERING FOR THEIR RECORDS. |
| |
| SIDEWALK AND DRIVEWAY REQUIREMENTS: |
| |
| 1.ALL BROKEN SIDEWALKS ALONG THE |
| PROPERTY (ALL SIDES) MUST BE REPLACED. |
| |
| 2.ALL DRIVEWAYS THAT WILL NOT BE USED |
| MUST BE REMOVED AND THE REGULAR CURBS (& |
| GUTTERS) MUST BE REPLACED. |
| |
| 3.ALL BROKEN UP CURBS (& GUTTERS) MUST |
| BE REPLACED. |
| |
| 4.ALL DRIVEWAY APPROACHES MUST BE (AT A |
| MINIMUM) PER CITY STANDARD DETAIL INDEX. |
| |
| 5.ALL GRADES FOR CITY SIDEWALKS WILL BE |
| SET BY THE CITY SURVEY CREW, CALL 659- |
| 8040 AND ASK FOR ED RYAN TO SET UP AN |
| APPOINTMENT. |
| |
| SANITATION: |
| |
| IF TO BE PICKED UP BY THE CITY THEN THE |
| FOLLOWING REQUIREMENTS MUST BE MET.IF |
| THE CONTRACTOR WISHES TO CHANGE ANY OF |
| THE FOLLOWING REQUIREMENTS HE WILL NEED |
| TO MEET WITH PETE SPATARA OF THE |
| SANITATION DIVISION AND SUBMIT THE |
| CHANGES TO BUILDING AND ZONING FOR |
| INCLUSION IN THE BUILDING PLAN SETS: |
| |
| 1.DUMPSTER MUST HAVE A MINIMUM OF 12'-6" |
| OPENING BETWEEN THE GATE POSTS. |
| |
| 2.INTERIOR DIMENSIONS OF THE ENCLOSURE |
| MUST BE A MINIMUM OF 12'-6" WIDE AND 12' |
| DEEP.A CONCRETE PARKING STOP BARS 10' |
| LONG MUST BE CENTERED (FROM GATES) AND |
| INSTALLED 18" FROM THE BACK WALL.STEEL |
| BARS WILL BE DRILLED THRU THE STOP BAR |
| AND INTO THE INTERIOR FLOOR OF THE |
| ENCLOSURE TO STOP THE STOP BAR FROM |
| MOVING WHEN THE DUMPSTER IS SET INSIDE. |
| |
| 3.THE OPENING OF THE DUMPSTER ENCLOSURE |
| MUST BE ANGLED SO THAT A 40' LONG TRUCK |
| WITH THE FORKS EXTENDED CAN APPROACH THE |
| OPENING AND PICK UP THE DUMPSTER WITHOUT |
| MAKING A SHARP TURN. |
| |
| THESE REVIEW COMMENTS (ENG 3 & 4) |
| REPLACE ENG 1& 2. |