2001-01-08 00:00:00THE AMOUNT OF REQUIRED PLUMBING FIXTURES
 SHALL COMPLY W/SPC TABLE 407.
 THE CALCULATIONS SUBMITTED BY REG ARCH.
 FOR REQD.FIXTURES DON'T COMPLY W/SPC.
 NO PROVISIONS ARE SHOWN FOR FUTURE
 PLUMBING.
  
 SUBMIT HANDICAP DETAIL FOR DRINKING
 FOUNTAIN.COMPLY W/FACBC SEC.4.15.
  
 CALCULATIONS FOR OVERFLOW DRAINAGE ARE
 NOT CLEAR.SUBMIT CORRECT CALCULATIONS.
 COMPLY W/SPC SEC.1109.1,1109.3,AND
 APPENDIX "A" AND TABLE A101.2 OF SPC.
  
 SHT.P-2-SQ.FT.AREA ON ROOF DRAINS DOES
 NOT MATCH SHT.P-4.CLARIFY.
  
 RELIEF LINE SHALL DISCHARGE TO EXTERIOR
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 507.6.
  
 VENTS FOR TOILET ROOMS SHALL BE 3" PER
 TABLE 920.2.
  
 SIZING OF HORIZONTAL SANITARY DRAINS
 SHALL COMPLY W/SPC TABLE 714.1.(TOILET
 ROOMS)AND 714.2.
 APPROVED PLUMBER TO SUBMIT SEPERATE
 PERMIT PRIOR TO STARTING ANY WORK. WRS