2001-01-08 00:00:00CLEARLY SHOW INSIDE DIMENSIONS OF TOILET
 ROOMS.(L X W)COMPLY W/FACBC SEC.4.16.2
 AND FIG.28.
  
 CLEARLY SHOW HEIGHT DIMENSIONS OF ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/FACBC 1997 ED.
  
 SHOW FIXTURE CLEARANCE OF H.C.WATER
 CLOSETS.COMPLY W/FIGURE 28 OF FACBC.
  
 A DRINKING FOUNTAIN IS REQD.ON EACH
 FLOOR AND SHALL BE H.C.ACCESSIBLE PER
 SPC 407 & FACBC 4.1.3.(10)(A).
  
 INDICATE OCCUPANT LOAD PER TABLE 407 OF
 SPC AND COMPLY W/TABLE 407 FOR TYPES &
 AMOUNT OF PLBG.FIXTURES REQD.
  
 SUBMIT CALCULATIONS FOR OVERFLOW DRAIN-
 AGE REQS.PER SBC SEC.1604.6.2.,
 1517.6.4.3
  
 WALLS IN TOILET ROOMS SHALL BE NON-
 ABSORBENT TO A HEIGHT OF 4'PER SBC
 1204.2.
  
 2" PIPE SHALL BE SLOPED A MIN. OF 1/4"
 PER FT. PER SPC 705.2.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.2.
  
 WATER HEATER SHALLBE READILY ACCESS-
 IBLE PER SPC SEC.501.7.PROVIDE A FIXED
 LADDER OR RELOCATE EWH TO FLOOR.
 HEATER ON FLOOR.
  
 WATER RISER SHOWS 1/2" LINE SUPPLYING
 C.W.SYSTEM.COMPLY W /SPC SEC.607.