Plan Review Notes For Permit 99100504 |
Permit Number |
99100504 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CLEARLY SHOW INSIDE DIMENSIONS OF TOILET | | ROOMS.(L X W)COMPLY W/FACBC SEC.4.16.2 | | AND FIG.28. | | | | CLEARLY SHOW HEIGHT DIMENSIONS OF ALL | | HANDICAP FIXTURES AND APPURTENANCES. | | COMPLY W/FACBC 1997 ED. | | | | SHOW FIXTURE CLEARANCE OF H.C.WATER | | CLOSETS.COMPLY W/FIGURE 28 OF FACBC. | | | | A DRINKING FOUNTAIN IS REQD.ON EACH | | FLOOR AND SHALL BE H.C.ACCESSIBLE PER | | SPC 407 & FACBC 4.1.3.(10)(A). | | | | INDICATE OCCUPANT LOAD PER TABLE 407 OF | | SPC AND COMPLY W/TABLE 407 FOR TYPES & | | AMOUNT OF PLBG.FIXTURES REQD. | | | | SUBMIT CALCULATIONS FOR OVERFLOW DRAIN- | | AGE REQS.PER SBC SEC.1604.6.2., | | 1517.6.4.3 | | | | WALLS IN TOILET ROOMS SHALL BE NON- | | ABSORBENT TO A HEIGHT OF 4'PER SBC | | 1204.2. | | | | 2" PIPE SHALL BE SLOPED A MIN. OF 1/4" | | PER FT. PER SPC 705.2. | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | SEC.610.4.2. | | | | WATER HEATER SHALLBE READILY ACCESS- | | IBLE PER SPC SEC.501.7.PROVIDE A FIXED | | LADDER OR RELOCATE EWH TO FLOOR. | | HEATER ON FLOOR. | | | | WATER RISER SHOWS 1/2" LINE SUPPLYING | | C.W.SYSTEM.COMPLY W /SPC SEC.607. |
|