Plan Review Notes For Permit 99100473 |
Permit Number |
99100473 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO**************** | | | | 1)NOTE:AS PER ART:110-9/215-5 NEED TO | | SUBMIT AIC RATING OF EQUIPMENT BEING | | INSTALLED (MAINS AND BRANCH BREAKERS) | | AIC RATING IS FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | 2)NOTE:AS PER ART;210-52D PLEASE HAVE | | BATH CIRCUT LISTED ON PANEL SCHEDULE. | | 3)NOTE:AS PER ART:210-63 A WP GFI RECEPT | | IS REQ`D FOR A/C UNIT AND IS TO BE | | WITHIN 25`. | | | | PLEASE HAVE THE ABOVE SUBMITTED FOR | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | ELECTRICAL INSPECTION IS CALLED IN. |
|