Plan Review Notes
Plan Review Notes For Permit 99100473
Permit Number 99100473
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:AS PER ART:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT BEING
 INSTALLED (MAINS AND BRANCH BREAKERS)
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART;210-52D PLEASE HAVE
 BATH CIRCUT LISTED ON PANEL SCHEDULE.
 3)NOTE:AS PER ART:210-63 A WP GFI RECEPT
 IS REQ`D FOR A/C UNIT AND IS TO BE
 WITHIN 25`.
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.