Plan Review Notes For Permit 99100381 |
Permit Number |
99100381 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE "A0". PROVIDE ELEVATION | | CERTIFICATE. | | 2-BEDROOM #2 WINDOWS DON'T MEET THE MIN. | | SIZE REQUIREMENTS OF SEC 1005.4.4 OF | | SBC 1997. REVISE ORIGINAL DWG AS REQ'D | | 3-SLIDING GLASS DOORS SPECIFIED ARE | | BIGGER THAN THE ONES IN PRODUCT | | APPROVAL. NEED ANOTHER PRODUCT | | APPROVAL OR SITE SPECIFIC ENGINEERING. | | -STORM PANELS: UPDATE INSTALLATION | | SCHEDULE (AS PER CITY SAMPLE) AND KEY | | PLAN. HIGHLIGHT SPECIFIC MOUNTING | | CONDITIONS AND ANCHORS TO BE USED. | | -PROVIDE PRODUCT APPROVAL FOR ENTRY | | DOOR WITH SIDELITE ASSEMBLY. | | 4-SOIL TEST REPORT TO BE SIGNED AND | | SEALED AND PROVIDE COPIES OF THE | | BORING TESTS. | | 5-REVISE SIZE OF WINDOWS IN MASTER SUITE | | TO MEET TABLE 600 SBC 1997. | | 6-SEE COMMENTS ON PLANS AND REVISE ALL | | ORIGINAL DRAWINGS AS REQUIRED. |
|