Plan Review Notes
Plan Review Notes For Permit 99100227
Permit Number 99100227
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT REVISED RISER
 LOAD CALCULATION. TO INCLUDE DISPLAY
 LIGHTING LOAD AS A CONTINUOUS LOAD.
 FIGURED AT 125% AS PER ART;220-3A
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE ROUGH
 ELECTRICAL INSPECTION.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved