2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTOR REQ`D OUTSIDE BEDROOM #2
 ALSO SMOKE DETECTOR NEEDS TO BE IN THE
 IMMEDIATE VICINITY OUTSIDE BEDROOM #3.
 2)NOTE: AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER/ISLAND ARE TO BE
 GFI/GFI PROTECTED.
 3)NOTE:NEED TO REVISERISER DIAGRAM
 SHOWINGSEPARATE FEEDS TO MAIN DISC.`S
 AS PER ART:373-8 PANELS/DISC. ARE NOT TO
 BE USED AS RACEWAYS.
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRSR ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.