2001-01-08 00:00:00 | ***************PROVISO***************** | | | | 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | SMOKE DETECTOR REQ`D OUTSIDE BEDROOM #2 | | ALSO SMOKE DETECTOR NEEDS TO BE IN THE | | IMMEDIATE VICINITY OUTSIDE BEDROOM #3. | | 2)NOTE: AS PER ART:210-8-A-6 ALL OUTLETS | | SERVING KITCHEN COUNTER/ISLAND ARE TO BE | | GFI/GFI PROTECTED. | | 3)NOTE:NEED TO REVISERISER DIAGRAM | | SHOWINGSEPARATE FEEDS TO MAIN DISC.`S | | AS PER ART:373-8 PANELS/DISC. ARE NOT TO | | BE USED AS RACEWAYS. | | | | PLEASE HAVE THE ABOVE SUBMITTED FOR | | REVIEW AND APPROVAL BEFORE FIRSR ROUGH | | ELECTRICAL INSPECTION IS CALLED IN. |
|