Plan Review Notes
Plan Review Notes For Permit 99091008
Permit Number 99091008
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-ROYAL WALL SYSTEM DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997. CALCULATIONS
 ARE INCORRECT.
 2-WHEN WALL FINISHES CONTRIBUTE TO GET
 THE TOTAL FIRE RESISTANCE OF THE WALL,
 THEN, THEY SHALL BE INSTALLED AS PER
 SECTION 709.3.1.6 SBC 1997.
 PROVIDE SPECIFICATIONS.
 3-PROVIDE COMPLETE DETAILS AND SPECS FOR
 FOR CONCRETE PANELS WITH ROUND AND
 ARCHED OPENINGS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS.SEC 104.2.2 OF AMENDMENTS
 5-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED IN THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH. SECTION 104.2.2
 CITY AMENDMENTS.
 7-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAILS FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.
 8-PROVIDE COMPLETE SET OF PRODUCT
 APPROVALS, INCLUDING ENTRY DOORS,
 ROUND AND ARCHED WINDOWS, WINDOW AT
 LIVING AREA, ETC.
 9-UPDATE ALL ENGINEERED TRUSS DRAWINGS.
 CUT AND PASTE IS NOT ACCEPTABLE.