Plan Review Notes For Permit 99091008 |
Permit Number |
99091008 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************PROVISO******************** | | | | 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO | | SUBMIT AIC RATING OF EQUIPMENT,MAINS, | | AND BRKRS. FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | GFI/GFI PROTECTED. | | 3)NOTE: EQUIPMENT GROUNDING CONDUCTOR | | IS NOT TO BE INSTALLED FROM METER TO | | FIRST MEANS OF DISC.ONLY FROM FIRST | | MEANS OF DISC.TO PANEL. | | 4)NOTE; AS PER ART: 210-63 RECEPT. REQD` | | FOR A/C EQUIPMENT. |
|