2001-01-08 00:00:00************PROVISO********************
  
 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT,MAINS,
 AND BRKRS. FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 3)NOTE: EQUIPMENT GROUNDING CONDUCTOR
 IS NOT TO BE INSTALLED FROM METER TO
 FIRST MEANS OF DISC.ONLY FROM FIRST
 MEANS OF DISC.TO PANEL.
 4)NOTE; AS PER ART: 210-63 RECEPT. REQD`
 FOR A/C EQUIPMENT.