2001-01-08 00:00:00 | REVISION: |
| ROYAL WALL SYSTEM IN LIEU OF CBS. |
| |
| CHECKLIST: |
| 1-FIRE RATED WALL DOESN'T MEET THE |
| REQUIREMENTS FOR SECTIONS 709.2.1.4.4 |
| AND 709.2.1.4.5 SBC 1997. (CALCS ARE |
| INCORRECT). |
| 2-WHEN WALL FINISHES ARE ASSUMED TO |
| CONTRIBUTE TO THE TOTAL FIRE |
| RESISTANCE OF THE WALL, THEN THEY |
| SHALL BE INSTALLED AS PER SECTION |
| 709.3.1.6 SBC 1997. |
| 3-PROVIDE COMPLETE DETAILS AND SPECS |
| FOR CONCRETE PANELS WITH ROUND AND |
| ARCHED OPENINGS. SEC 104.2.2 OF CITY |
| AMENDMENTS TO SBC 1997. |
| 4-PROVIDE INFORMATION SHOWING THE R |
| VALUE (12.9) CALCULATED IN THE ENERGY |
| CALCULATIONS. SEC 104.2.2 CITY AMENDM. |
| 5-PROVIDE COPIES OF APPROVED DRAWINGS |
| REFERENCED ON THE PRODUCT APPROVAL. |
| 6-PROVIDE COMPLETE DETAILS AND SPECS FOR |
| COLUMN AT REAR PORCH. |
| SEC. 104.2.2 CITY AMENDMENTS. |
| |
| FROM PREVIOUS PROVISO DATED 10/30/99: |
| 1-PROVIDE FULL SET OF PRODUCT APPROVALS. |
| 2-UPDATE ALL ENGINEERED TRUSSES. CUT AND |
| PASTE IS NOT ACCEPTABLE. |
| 3-STORM PANELS: |
| -PROVIDE A COMPLETE INSTALLATION |
| SCHEDULE AS PER CITY SAMPLE. |
| -PROVIDE DETAIL FOR INSTALLATION OF |
| STORM PANELS AT FRONT WINDOWS. SEE |
| EXTERIOR SILL DETAIL AND INSTALLATION |
| SCHEDULE. |