Plan Review Notes
Plan Review Notes For Permit 99091004
Permit Number 99091004
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00REVISION:
 ROYAL WALL SYSTEM IN LIEU OF CBS.
  
 CHECKLIST:
 1-FIRE RATED WALL DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997. (CALCS ARE
 INCORRECT).
 2-WHEN WALL FINISHES ARE ASSUMED TO
 CONTRIBUTE TO THE TOTAL FIRE
 RESISTANCE OF THE WALL, THEN THEY
 SHALL BE INSTALLED AS PER SECTION
 709.3.1.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CONCRETE PANELS WITH ROUND AND
 ARCHED OPENINGS. SEC 104.2.2 OF CITY
 AMENDMENTS TO SBC 1997.
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS. SEC 104.2.2 CITY AMENDM.
 5-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED ON THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH.
 SEC. 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO DATED 10/30/99:
 1-PROVIDE FULL SET OF PRODUCT APPROVALS.
 2-UPDATE ALL ENGINEERED TRUSSES. CUT AND
 PASTE IS NOT ACCEPTABLE.
 3-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.