2001-01-08 00:00:00 | |
| APPROVED WITH PROVISO: |
| 1-PLEASE REVISE ALL ORIGINALS SHOWING |
| ALL CORRECTIONS/CLARIFICATIONS. |
| 2-PROVIDE SAFETY GLASS IN LIBRARY WINDOW |
| SEC. 2405.2 SBC 1997. |
| 3-REVISE ENTRY DOOR SIZE TO HAVE 32" MIN |
| CLEAR OPENING. TABLE 1004 SBC 1997. |
| 4-ENGINEERED TRUSS DRAWINGS: |
| -UPDATE ALL DETAILS. |
| -UPDATE DESIGN CRITERIA. |
| -ENGINEER OF RECORD TO REVIEW ALL TRUSS |
| DRAWINGS PRIOR TO SUBMITTAL. |
| 5-REVISE DESIGN CERTIFICATION FOR WIND |
| LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT |
| IS INCORRECT. (21'-0" PLUS OR MINUS). |
| 6-SPECIFY SIZE OF CEILINGS FANS. TABLE |
| 6-6 FLORIDA ENERGY CODE 1997 EDITION. |
| CREDIT FOR CEILING FANS WAS TAKEN IN |
| THE ENRGY CALCULATIONS. |
| 7-PROVIDE FULL SET OF PRODUCT APPROVALS |
| (MASTER PERMIT IS ON HOLD TILL ALL |
| PLANS AND PRODUCT APPROVALS ARE |
| PROPERLY CORRECTED). |
| 8-STORM PANELS: |
| PROVIDE A COMPLETE INSTALLATION |
| SCHEDULE AS PER CITY SAMPLE ATTACHED |
| AND KEY PLAN. |
| HIGHLIGHT SPECIFIC MOUNTING CONDITIONS |
| AND ANCHOR SCHEDULE. |
| 9-PROVIDE ATTIC ACCESS AT MAIN ROOF. |
| SEC. 2309.6 SBC 1997. |
| 10-PROVIDE COMPLETE SPECIFICATIONS FOR |
| CEILING AT FRONT AND BACK PORCHES. |
| SEC. 104.2.2 CITY AMENDMENTS. |
| 11-PROVIDE COMPLETE DETAILS AND SPECS |
| FOR MOUNTING OF AHU'S. |
| SEC. 104.2.2 CITY AMENDMENTS. |