2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRANCH BREAKERS.
 AIC RATING IS FIGURED FROM FAULT
 CURRENT CALCULATIONS.AS PER ARTS:110-9/
 215-5.
 2)NOTE:RISER DIAGRAM SHOWS EQUIPMENT
 GROUND BEING INSTALLED FROM METER TO
 MAIN DISCONNECT. EQUIPMENT GROUND IS
 ONLY TO BE INSTALLED AFTER FIRST MEANS
 OF DISC.
 3)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:AS PER ART:210-52H OUTLET REQ`D
 IN MASTER BEDROOM HALLWAY.
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.